UPC: 046188069316
Also known as: ES-521BXT, GES-521BXTThe UTC 521BXT self-diagnostic, two-wire smoke detector is a conventional direct-wire smoke detector with analog features such as remote maintenance/trouble reporting (CleanMe), drift compensation, and multi-criteria detection.
The 521BXT continually monitors its own sensitivity and operational status, and provides a visual and remote trouble condition if the unit drifts out of the sensitivity range or fail internal diagnostics.
The 521 BXT is equipped with both a rate-of-rise and fixed temperature sensor and operates on 6.5 - 33 VDC.
Also known as: ES-521BXT, GES-521BXT
Technical Specifications:
- Listings: 511 UL 268
- Reset time: 1 second minimum
- Mounting dimensions: 4.75 in. (12.1cm) diameter; 0.3 in. (0.8cm) height
- Detector head dimensions: 5 in. (12.7cm) diameter; 2 in. (5cm) height
- Drift compensation adjustment: 1.0%/ft. max
- UL 2-wire compatibility identifier: DIP switch 1 ON S09A, DIP switch 1 OFF S10A, S11A (RX models)
- Heat detector specifications rate of rise: - 15 F/min and >105 F (8.3 C/min and >40.6 C)
- Detector packaging: 10 detectors per carton
- Field wiring size: 12-24 AWG
- Color: White head and base
- RFI immunity: 20V/m minimum; 0-1000MHz
- Operating humidity range: 0 to 95% non-condensing
- Operating termperature: 32° to 100°F (0° to 37°C)
- Photoelectic sensitivity: 3.1% + 0.5 - 1.0%
- Alarm contacts: 500mA @ 36VDC (resistive)
- Aux. relay contacts: 2A @ 30VDC
- Typical alarm current (12/24V): up to 60mA max. if not limited by control panel
- Typical average standby current: 70 uA (12/24V)
- Maximum ripple: (pk to pk) 10% (V p-p)
- Voltage: DIP switch 1 ON for standard 12V operation (6.5-20 VDC), polarity sensitive
|
For more information about the UTC (Formerly GE Security/ESL) 521BXT, please
contact us.