The new WFDTN Series waterflow detectors from System Sensor consists of a rugged, NEMA 4-rated enclosure that is more damage resistant than previous metal designs. The waterflow detector is designed for both indoor and outdoor use, with the widest available temperature range, from 32F to 150F.
Both the WFDTN with incorporated timer and WFDTNRN with immediate activation fit any tee that has a 1 in. NPT branch, including: 1in., 1in., 1 in. and 2in. NPT threaded ferrous and brass tees; 1in., 1in., 1in. and 2in. copper sweat tees; Tyco, Spears, NIBBCO brand 1 in. CPVC tees. Twelve different clearly marked plastic paddles are available to fit different installation configurations.
UL-listed models are equipped with tamper-resistant cover screws to prevent unauthorized entry. Inside, two sets of SPDT (Form C) synchronized switches are enclosed in a durable terminal block with new layout designed to make wiring easy with wire ready terminals, COM terminals are on a different elevation, large barrier between switches and easy to read raised textured lettering all make wiring easy. An optional cover tamper switch is available, securely snaps into place, no tools required.
The WFDTN incorporates a mechanical time delay feature, which minimizes the risk of false alarm due to pressure surges or air trapped in the fire sprinkler system. The larger and easy to turn timer dial makes setting the waterflow detector easy with high contrast pad printed markings. The dial offers three tabs to help with turning, with one larger tab located on the dial position for approximately 60 seconds, a notch is also indicated on the dial to locate approximately 30 seconds making setting the detector in dimmly lit locations easy.
The WFDTN series is designed for accuracy and repeatability. The detector also offers improved performance during vibration in riser applications where detectors are exposed to a large in rush of water.
UPC: 783863045967
Also known as: BK-WFDTN
Technical Specifications:
- U.S. Patent Numbers: 5,213,205
- Triggering Threshold Bandwidth (Flow Rate): 4-10 GPM
- Static Pressure Rating: 375 PSI
- Pipe Size: 1 in. NPT
- Operating Temperature Range: 32F to 150F (0C to 60C)
- Maximum Surge: 18 Feet Per Second (FPS)
- Enclosure Rating: NEMA 4 suitable for indoor/outdoor use
- Cover Tamper Switch: Optional for UL and ULC models, part no. CTS
- Contact Ratings: Two sets of SPDT (Form C) 10.0 A, HP @ 125/250 VAC 2.5 A @ 6/12/24 VDC
- Conduit Entrances: Two openings for in. conduit. One open, one knock-out type
- Compatible Tee Fittings: 1in., 1in., 1in., 2in. ferrous and brass threaded tees; 1in., 1in., 1in., 2in. copper sweat tees; 1in. CPVC tees
|