The SYSTEM-SENSOR-D4120 4-wire photoelectric, low-flow, duct smoke detector senses smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, temperatures of 4F to 158F, and a humidity range of 0 to 95 percent (non-condensing). A plug-in sensor head offers improved false alarm immunity and simple installation, testing, and maintenance.
With its 2:1 sensor-to-power capability, the power board of the D4120 may be used to monitor a second sensor, D4S, simultaneously (i.e., supply and return side). As many as 50 InnovairFlex detectors can be interconnected. When one unit senses smoke, all interconnected detectors will switch their relays; only the detector sensing smoke will go into alarm, thus pinpointing the fire source.
The D4120 features a pivoting housing that fits both square and rectangular footprints and mounts to round or rectangular ductwork. The unit is equipped with a cover design isolates the sensor head from the low-flow feature for simple maintenance.
UPC: 783863034411
Also known as: BK-D4120
Technical Specifications:
- Alarm auxiliary contacts: (DPDT) ¼ HP @ 120 VAC
- Alarm initiation contacts: (SPST) 2.0A @ 30 VDC (resistive)
- Max. alarm current: 35 mA RMS @ 120VAC 60 Hz
- Max. standby current: 20 mA RMS @ 120VAC 60 Hz
- Alarm response time: 15 sec.
- Power up time: 35 sec. max.
- Reset time: (by power down) 0.6 sec. max.
- Reset time: (with RTS151) .03 to 0.3 sec.
- Reset Voltage: 10 VAC min
- Power Supply Voltage: 120 VAC, 50-60 Hz
- Air Duct Velocity: 100 to 4000 ft/min (0.5 to 20.32 m/sec)
- Weight: 2.5 lbs (1.14 kg)
- Square Dimensions: 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth
- Rectangular Dimensions: 14.38 in (37 cm) Length; 5 in (12.74 cm) Width; 2.5 in (6.36 cm) Depth
|