System Sensor Model BEAM1224 is a four-wire conventional reflected beam smoke detector, which is uniquely suited for protecting open areas with high ceilings, where other methods of smoke detection are difficult to install and maintain. It is to be used with UL Listed compatible control panels only. An advantage of this single-ended reflective design is that it is much easier to install than the dual-ended projected beam detectors. Alignment is quickly accomplished via an optical sight and a two-digit signal strength meter incorporated into the product. Another advantage of the BEAM1224 is that it is listed for operation in temperatures ranging from 22F to 131F. This means it can be used in open areas to provide early warning in environments where temperature extremes may exceed the capability of other types of smoke detectors.
BEAM1224 consists of a transmitter/receiver unit and a reflector. When smoke enters the area between the unit and the reflector, the smoke causes a reduction in the signal. When the smoke level reaches the predetermined threshold, an alarm is activated.
BEAM1224 has four standard sensitivity selections, along with two Acclimate settings (adjustable sensitivity). When one of the two Acclimate settings is selected, the detector will automatically adjust its sensitivity using advanced software algorithms to choose the optimum sensitivity for the specific environment.
UPC: 783863023712
Also known as: BK-BEAM1224
Technical Specifications:
- Average Alignment Mode Current: 28 mA max @ 24 VDC
- Average Fault Current: 8.5 mA max @ 24 VDC
- Average Alarm Current: 38.5 mA max @ 24 VDC
- Average Current During Testing: 500 mA max
- Average Standby Current: 17 mA Max @ 24VDC
- Voltage: 10.2 to 32 VDC
- Temperature: –22°F to 131°F (–30°C to 55°C)
- Protection Range: 16 ft. to 328 ft. (5m to 100m)
- Detector Dimensions: 10" H x 7.5" W x 3.3" D (254 mm x 191 mm x 84 mm)
|