System Sensor D4120 4-Wire Photoelectric Low-Flow Duct Smoke Detector


  • Also known as: BK-D4120

  • The SYSTEM-SENSOR-D4120 4-wire photoelectric, low-flow, duct smoke detector senses smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, temperatures of 4F to 158F, and a humidity range of 0 to 95 percent (non-condensing). A plug-in sensor head offers improved false alarm immunity and simple installation, testing, and maintenance.

    With its 2:1 sensor-to-power capability, the power board of the D4120 may be used to monitor a second sensor, D4S, simultaneously (i.e., supply and return side). As many as 50 InnovairFlex detectors can be interconnected. When one unit senses smoke, all interconnected detectors will switch their relays; only the detector sensing smoke will go into alarm, thus pinpointing the fire source.

    The D4120 features a pivoting housing that fits both square and rectangular footprints and mounts to round or rectangular ductwork. The unit is equipped with a cover design isolates the sensor head from the low-flow feature for simple maintenance.
    Features:
    • 4-Wire Photoelectric, integrated low-flow technology
    • Air velocity rating from 100 ft/min to 4,000 ft/min
    • (0.5 m/s to 20.32 m/sec)
    • Versatile mounting options: square or rectangular configuration
    • Plug-in sensor offers superb false alarm immunity and the latest sensor technology
    • Broad ranges for operating temperature (4F to 158F) and humidity (0% to 95% non-condensing)
    • Patented sampling tube installs from front or back of the detector with no tools required
    • Increased wiring space with a newly added -inch conduit knockout
    • One easy-access Test/Reset button and improved LED status
    • Patented interconnect feature for multi-fan shutdown
    • New high contrast terminal designations
    • Built-in short circuit protection from operator wiring errors
    • Field selectable settings for configuring the detector
    • Two DPDT Form-C relay contacts
    • 24 VAC/DC or 120 VAC
    • Backward compatibility with existing Innovair products, including remote accessories


    Technical Specifications:

    • Rectangular Dimensions: 14.38 in (37 cm) Length; 5 in (12.74 cm) Width; 2.5 in (6.36 cm) Depth
    • Square Dimensions: 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth
    • Weight: 2.5 lbs (1.14 kg)
    • Air Duct Velocity: 100 to 4000 ft/min (0.5 to 20.32 m/sec)
    • Power Supply Voltage: 120 VAC, 50-60 Hz
    • Reset Voltage: 10 VAC min
    • Reset time: (with RTS151) .03 to 0.3 sec.
    • Reset time: (by power down) 0.6 sec. max.
    • Power up time: 35 sec. max.
    • Alarm response time: 15 sec.
    • Max. standby current: 20 mA RMS @ 120VAC 60 Hz
    • Max. alarm current: 35 mA RMS @ 120VAC 60 Hz
    • Alarm initiation contacts: (SPST) 2.0A @ 30 VDC (resistive)
    • Alarm auxiliary contacts: (DPDT) HP @ 120 VAC


    UPC: 783863034411

    Average rating: 5.0, based on 2 reviews


    For more information about the System Sensor D4120, please contact us.

    Share your knowledge of this product with other customers... Be the first to write a review

    Browse for more products in the same category as this item:

    System Sensor > HVAC Systems Monitoring > Conventional > Duct Smoke Detectors
    System Sensor
    System Sensor > HVAC Systems Monitoring
    System Sensor > HVAC Systems Monitoring > Conventional
    Fire & Life Safety > Smoke Detectors > Duct Detectors
    Burglar Alarms > Smoke Detectors > Addressable Smoke Detectors
    Burglar Alarms > Smoke Detectors
    Fire & Life Safety > Smoke Detectors